TECHNO STEAM TRAPS

Innovative Steam Traps and Condensate Recovery Systems

BALL FLOAT STEAM TRAP

TGH3, TGH4A, TGH5

TGH3 4A 5

Detailed Product Description
Ball Float F & T Steam Trap with bimetallic air vent for chemistry 
Ball Float F&T Steam Trap with bimetallic air vent TGH3, TGH4A, TGH5

Quick Details:
Model:
TGH3, TGH4A, TGH5
Material: Casting Steel WCB, WC6
Working Media: Steam, Condensate Water
End Connection: Flange
Stainless Steel Internals

Model Number:

TGH3, TGH4A, TGH5

Standard or Nonstandard:

Standard

Structure:

Ball Float Steam Trap

Pressure:

High Pressure,0.01 – 5.0 MPa

Power:

Automatic

Material:

Casting Steel

Temperature of Media:

Up to 425 Deg. C

Media:

Steam, Water

Port Size:

1″ – 6″

Body Material:

WCB, WC6

Connection:

Flange

 

Specifications
F&T Float Steam Trap
Double Ported Balance Valve System
Small Size but Large Capacity
Built in Air Vent & Strainer
Stainless Steel Internals
Design Pressure: PN25,40, 63
Pressure: 0.01 – 5.0Mpa
Material: Casting Steel WCB, WC6
Temperature: 425 ℃
Working Media: Steam, Condensate Water
End Connection: Flange Ball Float Steam Traps utilize a ball and float mechanism to provide modulated condensate discharge. A float rises as the condensate enters the trap body. The float is attached to a seat mechanism that opens proportional to the condensate level. A Bi-Metal thermostatic bypass valve is incorporated in the trap mechanism to insure that all non- condensable gas are removed from the system.
Lever float steam traps are unaffected by pressure and discharge condensate continuously.

Float Steam Trap / Ball Float Steam Trap

TGH3, TGH4A, TGH5:

  • With double ported balance valve system, the trap is small in physical size large in discharge capacity, can show superiority in the low pressure condition.
  • Built in Bi-metal automatic air vent to prevent air locking, and rapid start-up is provided.
  • All internal parts are easily accessible without having to remove the trap from the line.

Applications:
Steam traps are suitable for large steam heating equipment of low pressure that used in industries of petroleum, chemistry, metallurgy, electric power, food, pharmacy, etc.
 Note:
Protection rod of the float must be removed after installation.